Inlet Thread: M30x1.5
Outlet Thread: G1/8x28
Gauge Connection Thread: M10x1x12.5
Dip Tube Thread: M16x1.5
Pressure Mpa: 2.3-2.8
Check Valve: Valve core
The installation position and layout of fire sprinkler heads are the primary guarantee of system effectiveness. According to national standards, sprinkler heads should be installed in the center, coordinated with the layout of the building decoration ceiling, and maintained in rows and lines with lamps, smoke detectors and other equipment to ensure the overall coordination and safety of the fire protection system.
Specific to the installation requirements of different types of sprinkler heads:
The distance between the splash plate and the top plate of upright and pendant standard sprinkler heads must be strictly controlled within the range of 75 to 150 mm. This distance range has been scientifically verified to ensure that the water spray coverage area can be guaranteed and the water spray obstruction caused by improper distance can be avoided.
The installation distance of the side wall sprinkler head should be controlled between 50 and 100 mm from the wall. This distance ensures that the sprinkler head can effectively cover its protection range. During installation, special attention should be paid to the direction of the sprinkler head being parallel to the wall to avoid blind areas of water spraying.
Special space layout: When the width of beams, air ducts, drainage pipes or bridges exceeds 1.2 meters, additional sprinklers must be installed below the belly of these obstacles to avoid affecting the normal operation of the sprinklers. For the ceiling space above the suspended ceiling, if the clearance height exceeds 800 mm and there are combustibles inside, sprinklers must be installed as required.
The pipe layout of the sprinkler system also has strict requirements. The main pipe should be installed below, while the sprinkler branch pipe should be located above the main pipe, and a certain slope should be formed in the direction of the main pipe. This design is intended to facilitate future maintenance and drainage operations of the system. There are also special requirements for the installation position of the water flow indicator at the bend of the pipe and near the valve. It should be at least 15cm away from the elbow and at least 60cm away from the valve.
The maintenance of the sprinkler system is a necessary measure to ensure its long-term reliable operation.
Any problems found during maintenance should be handled immediately and recorded. For example, when a nozzle is contaminated by paint, it should be replaced in time, loose pipe supports should be reinforced immediately, and valve leaks must be repaired immediately. All maintenance work should be reported in writing, including the inspection date, inspector, problems found, measures taken and verification results.